RFOB
MV 12/20 kV
RFOB (TriCab M6P)
braided MV power
12/20KV 90°C 
m |
ze m² |
Min. Bend Radius mm |
Nom. Cond. OD mm |
Nom. Ins. RT mm |
Nom. Ins. OD mm |
Nom. Bed. OD mm |
Nom. Cable OD mm |
Current Rating amp |
Fault Current Rating |
Approx. Wt. kg/km |
|---|---|---|---|---|---|---|---|---|---|---|
| 3c | 35 | 344 | 7.4 | 5.5 | 19.3 | 48.5 | 57.3 | 130 | 5.0 | 5067 |
| 3c | 50 | 364 | 8.8 | 5.5 | 20.8 | 51.6 | 60.7 | 159 | 7.2 | 5869 |
| 3c | 70 | 393 | 10.6 | 5.5 | 22.6 | 55.9 | 65.5 | 203 | 10.0 | 7130 |
| 3c | 95 | 417 | 12.3 | 5.5 | 24.3 | 59.5 | 69.6 | 246 | 13.6 | 8189 |
| 3c | 120 | 439 | 13.9 | 5.5 | 25.9 | 62.9 | 73.2 | 286 | 17.2 | 9386 |
| 3c | 150 | 456 | 15.1 | 5.5 | 27.1 | 65.4 | 76.0 | 330 | 21.5 | 10526 |
| 3c | 185 | 485 | 16.9 | 5.5 | 28.9 | 69.7 | 80.9 | 377 | 26.5 | 11924 |
| 3c | 240 | 512 | 18.9 | 5.5 | 30.9 | 74.0 | 85.4 | 445 | 34.3 | 14094 |
| Conductor Comparison - TriCab versus Class 5 & 6 (approximate no.of wires) |
| Size mm² | 50 | 70 | 95 | 120 | 150 | 185 | 240 | 300 | 400 | 500 | 630 |
|---|---|---|---|---|---|---|---|---|---|---|---|
| TriCab | 658 | 969 | 1216 | 1672 | 2052 | 2508 | 3256 | 4144 | 5368 | 6832 | 8784 |
| Class5 | 378 | 342 | 465 | 587 | 734 | 905 | 1174 | 1468 | 1958 | 1710 | 2155 |
| Class6 | 662 | 927 | 1258 | 1589 | 1987 | 1401 | 1817 | 2272 |