RFOB
MV 8.7/15 kV
RFOB (TriCab M5P)
braided MV power
8.7/15KV 90°C 
m |
ze m² |
Min. Bend Radius mm |
Nom. Cond. OD mm |
Nom. Ins. RT mm |
Nom. Ins. OD mm |
Nom. Bed. OD mm |
Nom. Cable OD mm |
Current Rating amp |
Fault Current Rating |
Approx. Wt. kg/km |
|---|---|---|---|---|---|---|---|---|---|---|
| 3c | 25 | 298.7 | 6.2 | 4.5 | 16.2 | 41.7 | 49.8 | 105 | 3.6 | 3845 |
| 3c | 35 | 315.2 | 7.4 | 4.5 | 17.3 | 44.2 | 52.5 | 130 | 5.0 | 4407 |
| 3c | 50 | 336.0 | 8.8 | 4.5 | 18.7 | 47.2 | 56.0 | 159 | 7.2 | 5197 |
| 3c | 70 | 361.1 | 10.6 | 4.5 | 20.6 | 51.1 | 60.2 | 203 | 10.0 | 6309 |
| 3c | 95 | 386.2 | 12.3 | 4.5 | 22.3 | 54.8 | 64.4 | 246 | 13.6 | 7315 |
| 3c | 120 | 410.7 | 13.9 | 4.5 | 23.9 | 58.6 | 68.4 | 286 | 17.2 | 8548 |
| 3c | 150 | 427.2 | 15.1 | 4.5 | 25.0 | 61.1 | 71.2 | 330 | 21.5 | 9658 |
| 3c | 185 | 453.5 | 16.9 | 4.5 | 26.9 | 65.0 | 75.6 | 377 | 26.5 | 10842 |
| 3c | 240 | 484.7 | 18.9 | 4.5 | 28.9 | 69.7 | 80.8 | 445 | 34.3 | 13155 |
| Conductor Comparison - TriCab versus Class 5 & 6 (approximate no.of wires) |
| Size mm² | 50 | 70 | 95 | 120 | 150 | 185 | 240 | 300 | 400 | 500 | 630 |
|---|---|---|---|---|---|---|---|---|---|---|---|
| TriCab | 658 | 969 | 1216 | 1672 | 2052 | 2508 | 3256 | 4144 | 5368 | 6832 | 8784 |
| Class5 | 378 | 342 | 465 | 587 | 734 | 905 | 1174 | 1468 | 1958 | 1710 | 2155 |
| Class6 | 662 | 927 | 1258 | 1589 | 1987 | 1401 | 1817 | 2272 |