RFOB
MV 3.6/6 KV
RFOB (TriCab M3P)
braided MV power
3.6/6KV 90°C 
m |
ze m² |
Min. Bend Radius mm |
Nom. Cond. OD mm |
Nom. Ins. RT mm |
Nom. Ins. OD mm |
Nom. Bed. OD mm |
Nom. Cable OD mm |
Current Rating amp |
Fault Current Rating |
Approx. Wt. kg/km |
|---|---|---|---|---|---|---|---|---|---|---|
| 1c | 16 | 121.8 | 5.0 | 2.5 | 10.9 | 15.3 | 20.3 | 94 | 2.3 | 596 |
| 1c | 25 | 131.0 | 6.2 | 2.5 | 12.1 | 16.6 | 21.8 | 111 | 3.6 | 700 |
| 1c | 35 | 137.7 | 7.4 | 2.5 | 13.3 | 17.7 | 23.0 | 140 | 5.0 | 817 |
| 1c | 50 | 147.5 | 8.8 | 2.5 | 14.7 | 19.1 | 24.6 | 171 | 7.2 | 992 |
| 1c | 70 | 160.3 | 10.6 | 2.5 | 16.5 | 21.0 | 26.7 | 221 | 10.0 | 1267 |
| 1c | 95 | 170.7 | 12.3 | 2.5 | 18.2 | 22.7 | 28.5 | 271 | 13.6 | 1474 |
| 1c | 120 | 181.2 | 13.9 | 2.5 | 19.8 | 24.3 | 30.2 | 316 | 17.2 | 1749 |
| 1c | 150 | 190.3 | 15.1 | 2.5 | 21.0 | 25.4 | 31.7 | 367 | 21.5 | 2048 |
| 1c | 185 | 207.5 | 16.9 | 2.5 | 22.8 | 27.7 | 34.6 | 422 | 26.5 | 2410 |
| 1c | 240 | 222.2 | 18.9 | 2.6 | 25.0 | 29.9 | 37.0 | 502 | 34.3 | 3005 |
| 1c | 300 | 241.7 | 21.5 | 2.8 | 28.0 | 32.9 | 40.3 | 581 | 42.9 | 3668 |
| 1c | 400 | 268.7 | 24.5 | 3.0 | 31.4 | 37.1 | 44.8 | 680 | 57.2 | 4533 |
| 1c | 500 | 293.8 | 27.3 | 3.2 | 34.6 | 40.7 | 49.0 | 782 | 71.5 | 5426 |
| 1c | 630 | 311.5 | 30.2 | 3.2 | 37.5 | 43.6 | 51.9 | 900 | 90.1 | 6632 |
| Conductor Comparison - TriCab versus Class 5 & 6 (approximate no.of wires) |
| Size mm² | 50 | 70 | 95 | 120 | 150 | 185 | 240 | 300 | 400 | 500 | 630 |
|---|---|---|---|---|---|---|---|---|---|---|---|
| TriCab | 658 | 969 | 1216 | 1672 | 2052 | 2508 | 3256 | 4144 | 5368 | 6832 | 8784 |
| Class5 | 378 | 342 | 465 | 587 | 734 | 905 | 1174 | 1468 | 1958 | 1710 | 2155 |
| Class6 | 662 | 927 | 1258 | 1589 | 1987 | 1401 | 1817 | 2272 |