RFOB
MV 3.6/6 KV

RFOB (TriCab B3P)
braided MV VFD/VSD power

3.6/6KV  90°C 
Si
m
ze
m²
Ea
m
rth
m²
Min. Bend
Radius mm
Nom. Cond.
OD mm
Nom. Ins.
RT mm
Nom. Ins.
OD mm
Nom. Bed.
OD mm
Nom. Cable
OD mm
Current Rating
amp
Fault Current
Rating 1s kA
Approx. Wt.
kg/km
3c 10 3c 2.5 137 4.0 2.5 10.0 27.8 34.2 62 1.4 1944
3c 16 3c 2.5 146 5.0 2.5 10.9 30.0 36.5 83 2.3 2288
3c 25 3c 4 158 6.2 2.5 12.1 32.6 39.5 105 3.6 2731
3c 35 3c 6 169 7.4 2.5 13.3 35.1 42.2 130 5.0 3274
3c 50 3c 10 184 8.8 2.5 14.7 38.6 45.9 159 7.2 4120
3c 70 3c 16 201 10.6 2.5 16.5 42.4 50.3 203 10.0 5297
3c 95 3c 16 217 12.3 2.5 18.2 46.1 54.3 246 13.6 6181
3c 120 3c 25 234 13.9 2.5 19.8 49.9 58.5 286 17.2 7577
3c 150 3c 25 245 15.1 2.5 21.0 52.4 61.3 330 21.5 8619
3c 185 3c 35 264 16.9 2.5 22.8 56.3 65.9 377 26.5 10165
3c 240 3c 50 290 18.9 2.5 25.0 62.1 72.4 445 34.3 13076

Conductor Comparison - TriCab versus Class 5 & 6 (approximate no.of wires)
Size mm²50 70 95 120 150 185 240 300 400 500 630
TriCab658 969 1216 1672 2052 2508 3256 4144 5368 6832 8784
Class5378 342 465 587 734 905 1174 1468 1958 1710 2155
Class6662 927 1258 1589 1987 1401 1817 2272
Issue 11.0